Rees, Inc.
405 S Reed Rd.
Fremont, IN 46737 US
Phone: 260.495.9811 • Fax: 260.495.2186
E-Mail: sales@reesinc.com Web site: www.reesinc.com
All Categories > 30.5 mm Control Units > Contact Blocks > Item # 50703-000  


Item # 50703-000, Contact Blocks

List Price $60.10

Features/Applications

This contact block is designed for use on ALL REES push button operators and selector switches.  Each captive terminal on the contact block will accept (2) #14 AWG stranded wires.

  • Gold plated contacts eliminate high resistance tarnishing

Electrical Ratings

“HEAVY DUTY – A600 / N150”

Listed under UL 508 – File # E 58589

Certified under CSA C22.2 – File # LR 3648

CE Compliant IEC/EN 60947-5-1

 

Environmental Temperature Range

Operating:  +32oF to +131oF (0oC to +55oC)

Storage:  -40oF to +185oF (-40oC to +85oC)

Note:  Operating temperatures at 0oC are based on the absence of freezing moisture and liquids.

 

Normal Potential

Normal Current

Inrush Current

110-120 aca volts

6.0 amp.

60.0 amp.

220-240 aca

3.0 amp.

30.0 amp.

440-480 aca

1.5 amp.

15.0 amp.

550-600 aca

1.2 amp.

12.0 amp.

115-125 dcb

2.2 amp.

-----

230-250 dcb

1.1 amp.

-----

a  Power factor 0.35 or less

b  Inductive loads as specified in Section 125 of Industrial

   Control Devices, Controllers and Assemblies, ANSI /

   NEMA ICS 2-1988

WARNING - DANGER

 

 

 

 

 

 

 

These products should only be used where point-of-operation guarding devices have been properly installed & maintained so that appropriate OSHA and ANSI B11.1 regulations & standards are met.  Misapplication of the products on machinery lacking effective point-of operation safeguards can cause serious injury to the operator of that machinery.

 

 

 

 

 

 

 

---------------------------------------------------------------------------------------------------------------------

 

 

 

 

 

 

 

AVERTISSMENT - DANGER

 

 

 

 

 

 

 

Ces produit doivent seulement être utilisés sur des postes à risque correctement sécurisés et entretenus afin d’être conforme aux standards et régulations en vigueur (CSA, CLC). Un mauvais usage de ces produits sur des machines et des postes de travail non sécurisés de manière efficace peut causer des blessures graves au technicien maniant ces machines.

 








Specifications

Contact Designation

C

Circuits

2

Normal Function

Open and Closed

Stroke

0.10 in. to Open
0.20 in. to Close

Block Height

1.18

Approx. Shipping Weight

0.10 lb